Properties
Value
Coding
Byte 16 Number of available event entries (unsigned integer 8,
maximum: 64)
Byte 17 First available event entry: EventQualifier
Table 6: INSTANCE values
Value
Definition
0
Unknown
1 ... 3
Reserved
4
Application
5 ... 7
Reserved
Table 7: SOURCE values
Value
Definition
0
Device (remote)
1
Master (local)
Table 8: TYPE values
Value
Definition
0
Reserved
1
Notification
2
Warning
3
Error
Table 9: MODE values
Value
Definition
0
Reserved
1
Event single
2
Event disappears
3
Event appears
Byte
18...19
First available event entry: EventCode
Event codes are defined by the manufacturer of the IO-
Link device.
The following bytes repeat the coding of the first available event
entry.
7.1.2.2.1.16
Profile entries
Profile entries
can be used to read out the number of implemented IO-Link profiles of a
connected IO-Link device on this port as well as all profile identification numbers.
NOTE
The byte count for this function is dynamic and depends on the number of implemented
profile entries (1 byte for the number of entries and 2 bytes for each entry).
7
SIG200 CONFIGURATION
40
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
8017853.1D0S/2021-11-04 | SICK
Subject to change without notice