Advanced commissioning
6.6 Drive control via Ethernet/IP
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
155
No. Service
Type Name
Value/explanation
20 get, set UINT16 Low Speed Lim p1080 minimum speed
21 get, set UINT16 High Speed Lim p1082 maximum speed
22 get, set
SINT
Speed Scale
p8982 Ethernet/IP ODVA speed scaling
29
get
Bool
Ref From Net
Internal - display of Net_Reference
0: Local
1: Network
Value in p1300
Ethernet/IP motor data object
0 U/f with linear characteristic
1 Open loop speed (frequency)
1 U/f with linear characteristic and FCC
0 Vendor-specific mode
2 U/f with parabolic characteristic
4 U/f with linear characteristic and ECO
7 U/f for parabolic characteristic and ECO
20 Speed control (without encoder)
2 Closed-loop speed control
Siemens Drive Object, Instance Number: 32C hex
Supported services
Class
•
Get Attribute single
Instance •
Get Attribute single
•
Set Attribute single
Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Instance Attribute
No.
Type Service Name
Value/explanation
2
INT16 get, set Commissioning state
p0010 commissioning parameter filter
3 … 18
WORD
get
STW1
STW1 bit-by-bit access:
Attr.3 = STW1.0
Attr.18 = STW1.15
19
WORD
get
Main setpoint
Main setpoint
20 …
35
WORD
get
ZSW1
ZSW1 bit-by-bit access:
Attr.20 = ZSW1.0
Attr.35 = ZSW1.15
36
WORD
get
Actual Frequency
Main actual value (actual frequency)
37
REAL
get, set Ramp Up Time
p1120[0] ramp-function generator ramp-up time
38
REAL
get, set Ramp Down Time
p1121[0] ramp-function generator ramp-
down time
39
REAL
get, set Current Limit
p0640[0] current limit
40
REAL
get, set Frequency MAX Limit
p1082[0] maximum speed
41
REAL
get, set Frequency MIN Limit
p1080[0] minimum speed
42
REAL
get, set OFF3 Ramp Down Time p1135[0] OFF3 ramp-down time
43
UINT32
/ BOOL
get, set PID Enable
p2200[0] technology controller enable