WAGO-I/O-SYSTEM 750
Fieldbus Communication 113
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
Table 82: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
43
specific
get/set
BK_revision_s
etting
UINT
Defines the major and minor
revision attributes of the
fieldbus coupler/controller.
0xFFFF: The major and minor
revision attributes are set by the
firmware by default.
0xXX00: The minor revision is
set to 0.
0x03XX: The major revision is
set to 3.
All other values are also valid.
45
specific
get
BK_LED_ERR_
CODE
UINT
Contains the error code
displayed using I/O LED blink
code.
46
specific
get
BK_LED_ERR_
ARG
UINT
Contains the error argument
displayed using I/O LED blink
code.
47
specific
get
BK_DIAG_VA
LUE
UINT
Contains diagnostic information
supplied from the I/O module.
This attribute must be read
before attribute 6 of this class.
This only contains valid data
when attribute 6 contains valid
data.
51
specific
get/set
BK_FBC_CFG UINT
Contains configuration settings
Bit 0: =1 turns off displaying
current diagnostic messages via
MS LED. The diagnostic
messages, however, are still
transmitted via the fieldbus. Any
change to this setting is only
applied after a power-on cycle.
Bit 1..15: reserved
Services
Table 83: Service
Service
Code
Service Name
Description
0x0E
Get_Attribute_Single
Returns the content of a specific attribute
0x10
Set_Attribute_Single
Modifies the content of a specific attribute