Instance 1
Table 50: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Value
Description
1
required
get
Vendor
UINT
40 (0x28) Vendor identification
2
required
get
Device
Type
UINT
12 (0x0C) Displays the device type
3
required
get
Product
Code
UINT
e.g., 306
(0x132),
for the
750-306
Displays a specific device
from a specific
manufacturer
4
required
get
Revision
Major/
Minor
Struct:
USINT/
USINT
e.g.,
“020b”
(FW02.11(
11))
Revision of the
DeviceNet
TM
device,
which represents the
“Identity Object”
5
required
get
Status
WORD
-
Device status
6
required
get
Serial_
number
UDINT
-
Serial number
7
required
get
Product
name
SHORT_
STRING
(num,char
char...)
e.g.,
“WAGO
750-306
V 3.0)”
for the
750-306
Identification
10
required
get/set
Heartbeat
Interval
USINT
0
Interval between 2
heartbeat messages in
seconds
Services
Table 51: Service
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Returns the content of a specific attribute
0x05
Reset
Invokes the reset service for the device
10.1.5.2.1.2 Message Router (0x02)
No attributes, no services
10.1.5.2.1.3 DeviceNet Object (0x03)
Instance 0
Table 52: Instance 0
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data
Type
Value Description
1
required
get
Revision UINT
0x02
Revision number of the class
definition for the “Identity