SHED_OPT: should be configured with any valid option, like “NormalShed_NormalReturn”.
2)
BLOCK_ERR = OutOfService
: AO block is not going to AUTO when MODE_BLK.Target = AUTO.
a.
AO block is not scheduled to execute. Include the AO block in a control strategy or application to
schedule its execution.
b.
CHANNEL is not properly configured.
c.
SHED_OPT is not properly configured.
BLOCK_ERR in Analog Input
1)
BLOCK_ERR = BlockConfiguration
: check the following parameters:
•
CHANNEL: it should be configured with a valid channel associated with TRD.
See Analog Input channels table for more details.
•
XD_SCALE: check if this parameter is configured with valid units
•
OUT_SCALE: check if this parameter is configured with valid units
•
L_TYPE: should be configured with any valid option, like “Direct”.
2)
BLOCK_ERR = SensorFailure
: an error occurred during the positioner calibration.
Repeat the calibration.
3)
BLOCK_ERR = OutOfService
: The AI block is not going to AUTO when MODE_BLK.Target = AUTO.
•
The AI block is not scheduled to run. Include the AI block in a control strategy or application to
schedule its execution.
•
CHANNEL is not properly configured.
•
L_TYPE is not properly configured.
•
XD_SCALE is not properly configured.
•
OUT_SCALE is not properly configured.