5/12/2017
TECH-538/D.W.O. 23160
Page 136 of 189
Table 30:
BLOCK_ALMS_ACT table (valid for the Transducer blocks)
Value
Meaning
0x00000000 None Active => No active block alarms
0x08000000 Fault State Active => Fault State is active in the Transducer block due to
an invalid input or mis-configuration
0x04000000 Invalid Mode => The computed actual mode for the block is not
supported, the blocks actual mode will go to out of service
0x02000000 Bad Output Configuration => Conflicting output channels have been
assigned. Please review channels assignments and make appropriate
corrections
0x01000000 Invalid Input => The target position is not valid for the current device
configuration
0x00800000 Out Of Service => Transducer block is out of service
0x00400000 No Output Channels => No output channels have been assigned, i.e.
there can be no action
0x00200000 Open without Close => An Open output channel has been assigned
without a channel Close
0x00100000 Conflicting Channels => Conflicting output channels have been assigned,
please review and correct
0x00080000 Both Contacts Closed => Both contacts are closed
0x40000000 Mode Error => The mode calculator detected an error
Table 31:
SIGNAL_MASK and MASKABLE_SIGNAL table
Value Meaning
0
No Selection => No signal is selected to generate discrete
1
Cycle Count 1 exceeds limits => Number of valve cycles exceeds the
Cycle Count limit.
2
Cycle Time exceeds limits => Cycle time exceeds limit set in
cycle_time_lim
4
Bad Xducer Status => Status of the Transducer block is not Good
5
Low Temp. Alarm exceeds limits => Threshold configured for this
parameter has been exceeded.
6
Hi Temp. Alarm exceeds limits => Threshold configured for this
parameter has been exceeded.