5/12/2017
TECH-538/D.W.O. 23160
Page 148 of 189
Index
Std.
Par.
Parameter mnemonic
Description / EDD Help
Valid Range
FF Default
FCT Default
Deep
Default
Units
Write
R/W
parameter has precedence over the
FINAL_VALUE_CUTOFF_HI.
28
STOP_LO_POS
1 - User defined low limit for valve
position that when reached will set a
stop lo position limit bit. The alert is
generated via the standard Field
Diagnostic mechanism as defined in
References (FOUNDATION™
Specification, Function Block
Application Process Part 1 – FF-890,
Rev FS 1.10) and (FOUNDATION™
Specification, Function Block
Application Process Part 2 – FF-891,
Rev FS 1.10).
2- It also limits the Set Point. This
parameter has precedence over the
FINAL_VALUE_CUTOFF_LO.
0
0
0
%
29
TRAVEL_ACCUM
Totalized travel value since last reset.
0
0
0
TAU
Read
only
30
TRAVEL_ACCUM_LIM
User defined limit of accumulator
value that will trigger alert
0
0
0
TAU
Read
Only
31
PSNR_FSTATE_VAL
User defined position in case of fault
state of transducer.
FINAL _VALUE
_RANGE
0
0
0
O/S,
Man
R/W
32
PSNR_FSTATE_OPT
Defines an action to be taken on a
transducer fault state. Enumerations
defined in Standard Tables (TN-016).
0: Hold Last Value
1: Fail Closed
2: Fail Open
3:
PSNR_FSTATE_VAL_D
4-7: Reserved
8-255: Mfg Specific
0: Hold Last
Value
0: Hold Last
Value
0: Hold Last
Value
E
R/W
33
CYCLE_CNTR
Totalized cycle counts since last clear.
A cycle is defined as a complete
movement from one end to another.
R/W
34
SIGNAL_ACTION
It defines the actuator movement
relative to the increasing command.
Enumerations defined in Standard
Tables (TN-016).
0: Increase to Open
1: Increase to Close
0: Increase to
Open
0: Increase
to Open
0: Increase
to Open
E
Man
R/W
35
READBACK_SELECT
Selects whether working position or
0: Final Position Value
0: Final Position
0: Final
0: Final
E
R/W
30
See also 9.2.3.12 for power failure condition
31
In the FF standard dictionary revision lower than the revision 3.80, the user may see two parameters using the label: “Signal Action”. This is a
defect in the standard dictionary fixed in the revision 3.80. The parameter with the wrong label is the parameter RATED_TRAVEL.
ld host systems may still use an old revision of the dictionary and therefore show the wrong parameter name, giving the impression that there are
two parameters with the same name (SIGNAL_ACTION). It’s not difficult to pick the right SIGNAL_ACTION parameter because the SIGNAL
ACTION has only two options available.