5/12/2017
TECH-538/D.W.O. 23160
Page 146 of 189
Index
Std.
Par.
Parameter mnemonic
Description / EDD Help
Valid Range
FF Default
FCT Default
Deep
Default
Units
Write
R/W
10
Y
TRANSDUCER_TYPE
Identifies the transducer that follows.
See Standard Tables
(TN-016)
Standard
Analog Valve
Standard
Analog
Valve
Standard
Analog
Valve
E
Read
only
11
Y
TRANSDUCER_TYPE_VER
The version of the transducer
identified by TRANSDUCER_TYPE in
the form 0xAABB where AA is the
major revision of the transducer
specification on which the transducer
is based, and BB is a revision number
assigned and controlled by the
manufacturer of the device.
See parameter
description
0x1100
0x1100
0x1100
Read
only
12
XD_ERROR
One of the error codes defined in
Section 4.4 XD_ERROR and Block
Alarm Subcodes below.
XD_ERROR and Block
Alarm Subcodes
E
Read
only
13
COLLECTION_DIRECTORY
A directory that specifies the number,
starting indices, and EDD Item IDs of
the data collections in each
transducer within a transducer block.
For further information, please refer
to Section 3.4.8 above.
Legacy, array with
one element = 0.
0
0
0
None
Read
only
14
FINAL_VALUE
The requested valve position and
status written by an analog Function
Block.
0
0
0
None
Man
See
note 1
15
FINAL_VALUE_RANGE
The High and Low range limit values,
the engineering units code and the
number of digits to the right of the
decimal point to be used to display
the Final Value.
0
0
0
None
Man
See
note 2
16
FINAL_VALUE_CUTOFF_HI
If the FINAL_VALUE is more positive
than this value, the valve is forced to
its maximum high value (fully
opened).
FINAL_VALUE_RANGE,
+INF
0
0
0
None
O/S,
Man
17
FINAL_VALUE_CUTOFF_LO
If the FINAL_VALUE is more negative
than this value, the valve is forced to
its maximum low value (fully closed).
FINAL_VALUE_RANGE,
-INF
0
0
0
None
O/S,
Man
18
FINAL_POSITION_VALUE
The actual valve position and status;
can be used for a DI block and as the
READBACK_VALUE in a DO block.
0
0
0
None
Read
only
19
WORKING_POS
The actual measured feedback
position before de-characterization.
0
0
0
Read
only
20
WORKING_SP
The final command value to the
positioning algorithm after
characterization.
0
0
0
O/S,
Man
R/W
21
DEVIATION_DEADBAND
The user defined allowable deviation
before alert.
0
0
0
%
22
DEVIATION_TIME
The user defined allowable duration
in seconds of deviation before alert.
0
0
0
Sec
23
DEVIATION_VALUE
Difference between working setpoint
0
0
0
Read