830, 860
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed
Comfort
831, 861
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode Status
1-byte HVAC Mode
832, 862
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Basic Setpoint
Reference Setpoint
833, 863
1 Bit
I
C - - W -
DPT_Step
0/1
[Tx] Setpoint Step
0 = -0.5ºC; 1 = +0.5ºC
834, 864
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 - 670760.00
[Tx] Setpoint Offset
Float Offset Value
835, 865
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Setpoint Status
Current Setpoint
836, 866
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Basic Setpoint Status
Current Basic Setpoint
837, 867
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 - 670760.00
[Tx] Setpoint Offset Status
Current Setpoint Offset
838, 868
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Offset Reset
Reset offset
839, 869
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
840, 870
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
841, 871
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
842, 872
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
843, 873
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Cool)
PI Control (Continuous)
844, 874
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Heat)
PI Control (Continuous)
845, 875
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
PI Control (PWM)
846, 876
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
PI Control (PWM)
847, 877
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Cool
Temp >= (SBand)
=> "1"
848, 878
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Heat
Temp <= (Setpoint-Band)
=> "1"
849, 879
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] PI State (Cool)
0 = PI signal 0%; 1 = PI
signal greater than 0%
850, 880
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] PI State (Heat)
0 = PI signal 0%; 1 = PI
signal greater than 0%
881
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically