Actual signals and parameters 305
ENTER
SETPNT
State change when drive output frequency/speed enters the
reference area (ie, the difference is less than or equal to 4%
of the maximum reference).
51
AT SETPOINT State change when drive output frequency/speed equals the
reference value (= is within tolerance limits, ie, the error is
less than or equal to 1% of the maximum reference).
52
AI1 L1 & DI5
State change when AI1 value < par.
and when DI5 is active.
53
AI2 L2 & DI5
State change when AI2 value < par.
value and when DI5 is active.
54
AI1 H1 & DI5
State change when AI1 value > par.
value and when DI5 is active.
55
AI2 H2 & DI5
State change when AI2 value > par.
value and when DI5 is active.
56
AI1 L1 & DI4
State change when AI1 value < par.
value and when DI4 is active.
57
AI2 L2 & DI4
State change when AI2 value < par.
value and when DI4 is active.
58
AI1 H1 & DI4
State change when AI1 value > par.
value and when DI4 is active.
59
AI2 H2 & DI4
State change when AI2 value > par.
value and when DI4 is active.
60
DLY AND DI1
State change when delay time defined by parameter
has elapsed and DI1 is active.
61
DLY AND DI2
State change when delay time defined by parameter
has elapsed and DI2 is active.
62
DLY AND DI3
State change when delay time defined by parameter
has elapsed and DI3 is active.
63
DLY AND DI4
State change when delay time defined by parameter
has elapsed and DI4 is active.
64
DLY AND DI5
State change when delay time defined by parameter
has elapsed and DI5 is active.
65
DLY & AI2 H2
State change when delay time defined by parameter
has elapsed and AI2 value > par.
value.
66
DLY & AI2 L2
State change when delay time defined by parameter
has elapsed and AI2 value < par.
value.
67
DLY & AI1 H1
State change when delay time defined by parameter
has elapsed and AI1 value > par.
value.
68
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...