Model IR400 MODBUS
10
00DCh
Clock Time Low
Hi byte = Minute,
Lo byte second:
Calibration clock
time
Numeric
Value
0 – 59 minutes
0 – 59 seconds
R
00DDh
Calibration code
Calibration code
Numeric
Value
1 – zero, 2 -
calibration
R
00DEh
Reserved
Reserved
Numeric
Value
0
R
00DFh
Calibration
Event Count
Total Calibration
Event Count
Numeric
Value
0 - 65535
R
Table 8: List of Modbus Registers
1.4 IR400 Command Register Details
1.4.1 Analog
A read returns a value, which is proportional to the 0-20mA output current. The current is
based on a 16-bit value. The master scaling is 0 - 65535 Decimal which corresponds to
the IR400 scaling which is 0 - 21.7mA.
1.4.2 Operating Mode (Read/Write)
This register reports on the current operating mode for the IR400 detector. A Read
command returns the present IR400 mode, represented by the enabled bit. The following
table shows the mode represented by each bit in the 16-bit register.
Table 9: Bitmap for Operating Mode Register (Read-Only Access)
Bit
7 6 5 4 3 2 1
0
Mode
Not Used
Initial
Mode
Remove
Gas (CAL
Finished)
Apply
Gas
CAL
Pending
Zero
Mode
CAL
Mode
Run
Mode
Bit Value
80 hex
128
decimal
40 hex 64
decimal
20 hex
32
decimal
10 hex
16
decimal
8 hex
8 decimal
4 hex
4 decimal
2 hex
2
decimal
1 hex
1
decimal
Bit
15 14 13 12 11 10 9 8
Mode
Not Used
Not Used
Not Used
Not Used
Not Used
Zero &
CAL
Mode
Gas
Check
Mode
Not Used
Bit Value
8000 hex
32768
decimal
4000 hex
16384
decimal
2000 hex
8192
decimal
1000 hex
4096
decimal
800 hex
2048
decimal
400 hex
1024
decimal
200 hex
512
decimal
100 hex
256
decimal
1.4.2.1 Mode Descriptions (0x0001)
A Read command returns the present IR400 mode, represented by the enabled bit.
Descriptions of the modes are provided below.
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...