Model IR400 MODBUS
18
1.4.30 Running Time in seconds lo word (0x00B2)
This sets/reads hi word of device running time in seconds. This value must be
read/written after running time hi byte (register 0x00B1).
Table 15: Real Time Clock Time Format
Item
Number
Description
1
Hi Byte =Year, Low Byte = Month
2
Hi Byte = Day, Low Byte = Hour
3
Hi Byte = Minute, Low Byte = Second
1.4.31 Real-time Clock Year, Month (0x00B3)
This is used to read/write the real time clock. The high byte will be the year minus 2000.
The low byte will be a value from 1 to 12. To get or set real time, read or write
year/month (0x00B3) first, then day/hour (0x00B4), then min/sec (0x00B5)
1.4.32 Real-time Clock Day, Hour (0x00B4)
This is used to read/write the real time clock. The high byte will be the day of the month
from 1 to 31. The low byte will be the hour from 0 to 23. To get or set real time, read or
write year/month (0x00B3) first, then day/hour (0x00B4), then min/sec (0x00B5)
1.4.33 Real-time Clock Minute, Second (0x00B5)
This is used to read/write the real time clock. The high byte will be the minute from 0 to
59 and the low byte will be the seconds from 0 to 59. To get or set real time, read or write
year/month (0x00B3) first, then day/hour (0x00B4), then min/sec (0x00B5)
1.4.34 Power Cycle Flag (0x00B7)
This reads whether the time of day clock has been reset after a power has been re-
cycled to the unit. If the time has been reset, this flag will be = 0; otherwise the flag will =
1.
1.4.35 Event Index (0x00B7)
This is used to indicate which of the stored events the user would like to read. There are
5 event logs: Warning events, Alarm events, Fault events, Calibration events and
Maintenance events. Each of these event logs consist of 10 of their most recent
occurrences. The user is able to read the logs of each of these by setting this event index
followed by a reading of the desired event log. The event index is a number from 0 to 9.
Zero refers to the most recent event and 9 refers to the least recent event stored in the
log. For example to read time of the most recent Warning event in the Warning event log,
set this register to 0 and then read registers 0xB8 and 0xB9 (for the running time in
seconds) or read registers 0xBA, 0xBB, and 0xBC (for the clock time).
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...