Inputs for the function are the operating mode selections, setting parameters and measured and pre-
processed voltage magnitudes and binary input signals. Function outputs START, TRIP and BLOCKED
signals which can be used for direct IO controlling and also for user logic programming. The function
registers its operation into 12 last time-stamped registers and also generates general time stamped
ON/OFF events to the common event buffer from each of the three output signal. In instant operating
mode the function outputs START and TRIP events simultaneously with equivalent time stamp. Time
stamp resolution is 1ms. Function provides also cumulative counters for START, TRIP and BLOCKED
events.
In the following gure is presented the simpli ed function block diagram of the UV function.
Figure. 5.4.12. - 72. Simpli ed function block diagram of the UV function.
Measured input values
Analog voltage measurement values are used by the function. Function block always utilizes peak-to-
peak measurement from samples and the monitored magnitudes are fundamental frequency RMS
values. -20 ms averaged value is used for the pre-fault data.
Table. 5.4.12. - 117. Analogic magnitudes used by UV function.
Signal
Description
Time base
U
L12
RMS
Fundamental RMS measurement of voltage U
L12
/V
5 ms
U
L23
RMS
Fundamental RMS measurement of voltage U
L23
/V
5 ms
U
L31
RMS
Fundamental RMS measurement of voltage U
L31
/V
5 ms
U
L1
RMS
Fundamental RMS measurement of voltage U
L1
/V
5 ms
U
L2
RMS
Fundamental RMS measurement of voltage U
L2
/V
5 ms
U
L3
RMS
Fundamental RMS measurement of voltage U
L3
/V
5 ms
Table. 5.4.12. - 118. Measured magnitude selection setting.
Name
Description
Range
Step Default
Measured
magnitude
Selection of P-P or P-E voltages. Additionally U3 or U4 input can be
assigned as the voltage channel to be supervised.
0: P-P
Voltages
1: P-E
Voltages
2: U3Input
(2LL-U3SS)
3: U4InputSS
-
0: P-P
Voltages
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
128