Resetting characteristics can be set according to the application. Default setting is delayed with 60 ms
and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the operating time
during the release time, function will not trip if the input signal is not activated again during the release
time counting.
Events and registers
The CUB function generates events and registers from the status changes of start, trip and blocked. To
main event buffer it is possible to select status “On” or “Off” messages. The CUB function offers four
independent instances which events are segregated for each instance operation. Function includes 12
last registers where the triggering event of the function (start, trip or blocked) is recorded with time
stamp and process data values.
Table. 5.4.7. - 92. Event codes of the CUB-function instances.
Event Number
Event channel
Event block name
Event Code
Description
2048
32
CUB1
0
Start ON
2049
32
CUB1
1
Start OFF
2050
32
CUB1
2
Trip ON
2051
32
CUB1
3
Trip OFF
2052
32
CUB1
4
Block ON
2053
32
CUB1
5
Block OFF
2112
33
CUB2
0
Start ON
2113
33
CUB2
1
Start OFF
2114
33
CUB2
2
Trip ON
2115
33
CUB2
3
Trip OFF
2116
33
CUB2
4
Block ON
2117
33
CUB2
5
Block OFF
2176
34
CUB3
0
Start ON
2177
34
CUB3
1
Start OFF
2178
34
CUB3
2
Trip ON
2179
34
CUB3
3
Trip OFF
2180
34
CUB3
4
Block ON
2181
34
CUB3
5
Block OFF
2240
35
CUB4
0
Start ON
2241
35
CUB4
1
Start OFF
2242
35
CUB4
2
Trip ON
2243
35
CUB4
3
Trip OFF
2244
35
CUB4
4
Block ON
2245
35
CUB4
5
Block OFF
In the register of the CUB function recorded events are start, trip or blocked “On” event process data.
Table below presents the structure of CUB function register content. This information is available in 12
last recorded events for all provided instances separately.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
96