6 Application example: Modbus TCP
6.4 Parameterization of modules
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
129
6.4
Parameterization of modules
The parameters of the XI/ON-modules of one station can be accessed via register range
0×B000 to 0×B400.
For each module in the station, 64 bytes = 32 registers of parameter data are reserved.
The parameterization of XI/ON I/O-modules is described by means of the following examples:
• Example A:
Module 0:
- Changing the measurement range for channel 0 from
"0 to 20 mA" to "4 to 20 mA".
- Deactivation of channel 1 via parameter "channel".
• Example B:
Module 9:
Changing the baudrate from 500000 bps to 71000 bps.
Example A:
Module 0:
The parameter of the module (1. slot in the station) can be accessed via registers 0×B000 to
0×B01F.
1
Changing the measurement range for channel 0 from "0 to 20 mA" to "4 to 20 mA".
The module shows the following parameter data structure (1 byte of parameters per
channel):
Table 67:
Module
parameters
XN-2AI-
I(0/4...20MA)
A
default-
setting
Byte Bit
Parameter
Value
0/1
0
Current mode
0 = 0..20mA
A
1 = 4..20mA
1
Value representation
0 = Integer (15bit + sign)
A
1 = 12bit (left-justified)
2
Diagnosis
0 = release
A
1 = block
3
Channel
0 = activate
A
1 = deactivate