The drive control parameters could complete drive start, stop, and set running
frequency etc., via retrieving the drive’s state parameters, it could obtain the drive’s
running frequency, output current, output torque etc. Specific drive’s control
parameters and state parameters are listed in the following:
Drive’s Control Parameter Index
Register
Address
Parameter Name
Whether Save after Power off
0x3200
Control command Character
No
0x3201
Main setting
Main setting value is the running
frequency given.
0x3202
Running frequency setting
Yes
0x3203
Digit closed-loop given
Yes
0x3204
Pulse closed-loop given
Yes
0x3205
Analog output A01 setting
No
0x3206
Analog output AO2 setting
No
0x3207
Digit output DO setting
No
0x3208
Frequency proportion setting
No
0x3209
Virtual terminal control setting No
0x320A
Set accelerating time 1
Yes
0x320B
Set decelerating time 1
Yes
Drive’s State Parameter Index
Register
Address
Parameter Name
0x3300
Operation state character 1
0x3301
Actual operation value of the current main setting
0x3302
Slave model
0x3303
Drive model
0x3304
Software version
0x3305
Current running frequency
0x3306
Output Current
0x3307
Output Voltage
0x3308