Chapter 8: Using the Command Line Interface
407
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on
all outlets in sequence.
config:#
pdu outletSequenceDelay <outlet1>:<delay1>;<outlet2>:<delay2>;
<outlet3>:<delay3>;...
Separate outlet numbers and their delay settings with a colon. Outlets
followed by delays are separated with a semicolon.
Variables:
<outlet1>, <outlet2>, <outlet3> and the like are individual outlet
numbers or a range of outlets using a dash. For example,
3-8
represents outlets 3 to 8.
<delay1>, <delay2>, <delay3> and the like are the delay time in
seconds.
Note: Power-on sequencing is disabled in the latching mode. See
PX3
Latching Relay Behavior
(on page 150).
Setting the PDU-Defined Default Outlet State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of all outlets after
powering up the PDU.
config:#
pdu outletStateOnDeviceStartup <option>
Variables:
<option> is one of the options:
off, on or lastKnownState.
Option
Description
off
Switches OFF all outlets when the PX3 device
powers up.
on
Switches ON all outlets when the PX3 device
powers up.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...