CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
DI1 to DI8 Status
P012 = 10010000
Inactive = 0, Active = 1, and the DI1 status is the most significant bit (MSB).
Example:
DI1 = Active (+24 V); DI2 = Inactive (0 V);
DI3 = Inactive (0 V); DI4 = Active (+24 V);
DI5 = Inactive (0 V); DI6 = Inactive (0 V);
DI7 = Inactive (0 V); DI8 = Inactive (0 V);
This is equivalent to the binary sequence:
10010000
Which corresponds to the decimal number 144.
The Keypad displays will be as follows:
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P013
LCD = 0 or 1
Digital and Relay
LED = 0 to 255
Outputs DO1, DO2
[ - ]
RL1, RL2 and RL3
-
Status
Indicates on the Keypad LCD Display the status of the 2 Digital Outputs
of the I/O Expansion Board (DO1, DO2) and the 3 Relay Outputs of the
control board. Number 1 stands for Active and number 0 stands for Inactive,
in the following order: DO1, DO2, RL1, RL2, RL3.
The LED display shows a decimal value related to the status of the 5
Digital and Relay Outputs, where the status of each output is considered
one bit of a binary number where:
Inactive = 0, Active = 1, and the status of DO1 is the most significant bit
(MSB). The 3 least significant bits are always ‘0’.
Example:
DO1 = Inactive; DO2 = Inactive
RL1 = Active: RL2 = Inactive; RL3 = Active
This is equivalent to the binary sequence:
00101000
Which corresponds to the decimal number 40.
The Keypad displays will be:
DO1 to RL3 Status
P013 = 00101