Janu
ary 201
9
436 Legrand PDU User Guide
logfile
Specify the name of a text file where the Legrand PDU will append the log messages when interpreting
the USB drive contents.
If the specified file does not exist in the USB drive, it will be automatically created.
If this option is not set, no log messages are recorded. The disadvantage is that no feedback is available
if the Legrand PDU detects a problem with the USB drive contents.
firmware
Specify the name of a firmware binary file used to upgrade your Legrand PDU.
The specified firmware file must be compatible with your Legrand PDU and have an official Raritan
signature.
If the specified firmware file is the same as the current firmware version of your Legrand PDU, no
firmware upgrade is performed.
As of version 3.5.0, the default is to NOT permit any firmware
downgrade
via
USB
on Legrand power
products with "USB-A" port(s). To do this, the parameter "allow_downgrade" must be present and
properly set in the
fwupdate.cfg
file.
config
Specify the name of the configuration file containing device settings.
The suggested filename is
config.txt
. See
config.txt
(on page 437).
device_list
Specify the name of the configuration file listing all Legrand PDUs to configure and their device-specific
settings.
This file is required if any macros are used in the device configuration file "config.txt."
The suggested filename is
devices.csv
. See
devices.csv
(on page 439).
match
Specify a match condition for identifying a line or one Legrand PDU device in the device configuration file
"devices.csv."
The option's value comprises one word and one number as explained below:
The word prior to the colon is an identification property, which is either
serial
for serial number or
mac
for MAC address.
The number following the colon indicates a column in the
devices.csv
file.
For example,
mac:7
instructs the Legrand PDU to search for the MAC address in the 7th column of the
"devices.csv" file.
The default value is
serial:1
, making the Legrand PDU search for its serial number in the first column.
This option is used only if the "device_list" option has been set.
factory_reset
If this option is set to
true
, the Legrand PDU will be reset to factory defaults.
If the device configuration will be updated at the same time, the factory reset will be executed before
updating the device configuration.
bulk_config_restore
Specify the name of the bulk configuration file used to configure or restore the Legrand PDU.
Note: See
Bulk Configuration
(on page 262) for instructions on generating a bulk configuration file.