Chapter 6 Instruction and Flag List
XBC E-Type Main Unit
6-32
Ver. 1
Word
Bit
Variable
Function
Description
F002~3
F0028
_BPRM_ER
Basic parameter
Basic parameter error.
F0029
_IOPRM_ER
IO parameter
I/O configuration parameter error.
F002A
_SPPRM_ER
Special module parameter
Special module parameter is
Abnormal.
F002B
_CPPRM_ER
Communication module
parameter
Communication module parameter
is abnormal.
F002C
_PGM_ER
Program error
Program error.
F002D
_CODE_ER
Code error
Program Code error.
F002E
_SWDT_ER
System watchdog
System watchdog operated.
F0030
_WDT_ER
Scan watchdog
Scan watchdog operated.
F004
-
_CNF_WAR
System warning
Reports light error state of system.
F0041
_DBCK_ER
Backup error
Data backup error.
F0043
_ABSD_ER
Operation shutdown error
Stop by abnormal operation.
F0046
_ANNUM_WAR
External device error
Detected light error of external device.
F0048
_HS_WAR1
N/A
F0049
_HS_WAR2
N/A
F0054
_P2P_WAR1
P2P parameter 1
P2P – parameter 1 error.
F0055
_P2P_WAR2
N/A
F0056
_P2P_WAR3
N/A
F005C
_CONSTANT_ER
Constant error
Constant error.
F009
-
_USER_F
User contact
Timer used by user.
F0090
_T20MS
20ms
As a clock signal available at user program, it
reverses On/Off every half period. Since clock
signal is dealt with at the end of scan, there may
be delay or distortion according to scan time. So
use clock that’s longer than scan time. Clock
signal is Off status at the start of scan program
and task program.
_T100ms clock
50ms 50ms
F0091
_T100MS
100ms
F0092
_T200MS
200ms
F0093
_T1S
1s Clock
F0094
_T2S
2 s Clock
F0095
_T10S
10 s Clock
F0096
_T20S
20 s Clock
F0097
_T60S
60 s Clock
F0099
_On
Ordinary time On
Always On state Bit.
F009A
_Off
Ordinary time Off
Always Off state Bit.
F009B
_1On
1scan On
First scan On Bit.
F009C
_1Off
1scan Off
First scan OFF bit.
F009D
_STOG
Reversal
Reversal every scan.