Chapter 6 Instruction Details
XBC E-Type Main Unit
6-62
Ver. 1
6.14.2 OUT Syy.xx
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
OUT
S
-
-
-
-
-
-
- O -
-
-
-
-
-
-
-
1
-
-
-
Operand
Description
Data Type
Syy.xx
As S device contact, yy is for group number, xx for step number.
Group Number is available 0~127, and step number 0~99
BIT
1) OUT Syy.xx (Subsequent Input Preferred)
(1) Inversely from SET Syy.xx, applicable step operates if input condition contact is On regardless of step
sequence.
(2) Only one step number will be On in the same group even if lots of input condition contacts are On. Finally
program is on priority.
(3) Present step number if On will be self-held to keep On state although input contact is Off.
(4) OUT Syy.xx Instruction will be cleared if Sxx.00’s input contact is On.
2) Program Example
Subsequent Input Preferred Control Program with S02 group used
[Ladder Program]
[Mnemonic Program]
No
P00020
P00021
P00022
P00023
S02.01
S02.23
S02.98
S02.00
1
On
Off
Off
Off
On
2
On
On
Off
Off
On
3
On
On
On
Off
On
4
On
On
On
On
On
( )
OUT Syy.xx
Syy.xx
S
Step Mnemonic
Operand
0
LOAD
P00020
1
OUT
S02.01
2
LOAD
P00021
3
OUT
S02.23
4
LOAD
5
OUT
S02.99
6
LOAD
7
OUT
S02.00
P00022
P00023
P00022
P00023
P00021
S02.23
S02.99
S02.00
P00020
S02.01
END