Chapter 6 Instruction Details
XBC E-Type Main Unit
6-312
Ver. 1
6.46 Special/Communication Module related Instruction
6.46.1 GET, GETP
Instruction
Area Available
Step
Flag
P M K
F
L
T
C
S
Z D.x R.x
Con
st
U
N
D
R
Error
(F110)
Zero
(F111)
Carry
(F112)
GET(P)
sl
-
-
-
-
-
-
-
-
-
-
-
O
-
-
-
-
4~7
-
-
-
S
-
-
-
-
-
-
-
-
-
-
-
O
-
-
-
-
D
O O O
-
O
-
-
-
-
-
-
-
O O O O
N
O O O
-
O
-
-
-
-
-
-
O O O O O
Operand
Description
Data Size
sl
Slot number where special module is installed (Set to the Hexadecimal)
WORD
S
Start address of internal memory in special module
WORD
D
Start address of Device in CPU which is saving the data to read
WORD
N
Number of data to read
WORD
[Flag Setting]
Flag
Description
Device Number
PUT/GET
Error
If there is no special module installed on specified slot
If PUT/GET instruction is not completed correctly
F0015 ~ F0022
1) GET
(1) This instruction is used to read the data of special module with memory.
(2) It saves N word data from special module’s memory (specified in S: address) specified in sl (special
module’s slot number) to internal device area specified in D.
(3) If there is no special module specified in sl (special module’s slot number), or GET instruction is not
completed correctly, applicable position bit of PUT/GET Error Flag, F0015~F0022(WORD) will be set.
(4) The setting method of sl (slot number of special module) is to set the 2 places of Hexadecimal. If sl ‘h10’
is same as below program, first number ‘1’ is a base number and second ‘0’ means a slot number.
M00021
GET h10 100 D00100 4
F0015
F0016
b15
b0
1
.
.
.
F0022
If there is no special module
in the Slot 0 of No.1 Base,
or Get instruction is not
completed correctly.
GET
means GET
P sl
GETP
D
N
S
sl
D
N
S