E-6
Compressed ASCII Commands
Date Code 20010625
SEL-311L Instruction Manual
CEVENT C
OMMAND
—SEL-311L
Display event report in compressed ASCII format by sending:
CEV [
n
S
x
L
y
L R C]
(parameters in [ ] are optional)
where:
n
event number (1–41 if LER = 15; 1–22 if LER = 30; 1–11 if LER = 60;
defaults to 1)
S
x
x
samples per cycle (4 or 16); defaults to 4
If S
x
parameter is present, it overrides the L parameter
L
y
y
cycles event report length (1–LER) for filtered event reports,
(1–LER+1) for raw event reports, defaults to 15 if not specified
L
16 samples per cycle; overridden by the S
x
parameter, if present
R specifies raw (unfiltered) data; defaults to 16 samples per cycle unless
overridden by the S
x
parameter. Defaults to 16 cycles in length unless
overridden with the L
y
parameter.
C specifies 16 samples per cycle, 15-cycle length
The relay responds to the
CEV
command with the nth event report as shown below. Items in
bold italics
will be replaced with the actual relay data.
The compressed ASCII reports contain both backup and differential protection information.
<STX>"FID","0143"<CR>
"
Relay FID string
",
"yyyy"<CR>
"MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","0ACA"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"FREQ","SAM/CYC_A","SAM/CYC_D","NUM_OF_CYC","EVENT",
"LOCATION","SHOT","TARGETS","IA","IB","IC","IP","IG","3I2","IAL","IBL","ICL","IAX",
"IBX","ICX","IAY","IBY","ICY","2606"<CR>
xxxx,xxxx,xxxx,xxxx,"xxxx",xxxx,xxxx,"xxxx",xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"IA","IB","IC","IP","IG","VA(kV)","VB(kV)","VC(kV)","VS(kV)","V1MEM","FREQ",
"VDC","IAL","IBL","ICL","IAX","IBX","ICX","IAY","IBY","ICY","IAT","IBT","ICT",
"TRIG","
Names of elements in the relay word separated by spaces
","A30C"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,z,"
HEX-ASCII Relay Word
","yyyy"<CR>
"
Analog and digital data repeated for each row of event report
"
"SETTINGS","yyyy"<CR>
"
Relay group, logic, and global settings as displayed with the showset command (surrounded
by quotes)
","yyyy"<CR><ETX>
where:
"xxxx" are the data values corresponding to the line labels.
"yyyy" is the 4-byte hex ASCII representation of the checksum.
"FREQ" is the power system frequency at the trigger instant.
"SAM/CYC_A" is the number of analog data samples per cycle (4 or 16).
"SAM/CYC_D" is the number of digital data samples per cycle (4 or 16).
"NUM_OF_CYC" is the number of cycles of data in the event report.
"EVENT" is the event type.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......