IF630 Programming 5/26/01
___________________________________________________________________________________________
Rev 3.0
63
CONTROL BY EVENT
Control-by-Event programming allows the user to create a matrix whereby selected groups of
input devices are logically arranged to selected groups of output devices or circuits. The
SmartStart
feature automatically assigns all input devices to select all output devices or
circuits.
In the device specific screens, input or output group numbers (1 - 256) can be assigned to
each device. Multiple devices can be assigned to a single group but each device can only be
assigned to a single group.
In the output programming menu for each device or circuit there is a field (Alr) for assigning
the Alarm level it will activate. The three levels of alarm, 1= pre-alarm, 2= 1st alarm and
3=2nd alarm. These levels combined with the CBE table determine when the circuit or
device will activate.
____________________________________________________________________________________________
CBE Programming
Control-by-Event "CBE" programming is dedicated to system wide ALARM functions.
Select "CBE" (#2) from the main "Programming Mode" menu to change or assign input
group assignment with the associated output group.
To select "logical" Group Inputs
1.
Select "CBE" (#2) from the main "Programming Mode" menu.
2.
Press
"
Enter
".
Enter Input Group#: XXX
Figure 13
3.
Using numeric keys, enter the corresponding input group number. The
group number will be displayed in the location as shown in Figure 14.
xxx
Enter Input Group: xxx
Figure 14
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...