262 Parameters
Activates fieldbus communication monitoring separately for
each control location (see section
The parameter is primarily intended for monitoring the
communication with EFB when it is connected to the
application program and not selected as a control source by
drive parameters.
0000b
0000b…0111b
EFB communication monitoring selection.
1 = 1
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400001.
The master defines the type of the data (input or output). The
value is transmitted in a Modbus frame consisting of two 16-
bit words. If the value is 16-bit, it is transmitted in the LSW
(least significant word). If the value is 32-bit, the subsequent
parameter is also reserved for it and must be set to
.
None
None.
0
CW 16bit
Control Word (16 bits).
1
Ref1 16bit
Reference REF1 (16 bits).
2
Ref2 16bit
Reference REF2 (16 bits).
3
SW 16bit
Status Word (16 bits).
4
Act1 16bit
Actual value ACT1 (16 bits).
5
Act2 16bit
Actual value ACT2 (16 bits).
6
CW 32bit
Control Word (32 bits).
11
Ref1 32bit
Reference REF1 (32 bits).
12
Ref2 32bit
Reference REF2 (32 bits).
13
SW 32bit
Status Word (32 bits).
14
Act1 32bit
Actual value ACT1 (32 bits).
15
Act2 32bit
Actual value ACT2 (32 bits).
16
CW2 16bit
Control Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
21
SW2 16bit
Status Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
24
RO/DIO control
word
31
AO1 data storage
Parameter
.
32
AO2 data storage
Parameter
.
33
-
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Value
0
Ext 1
1 = Communication monitoring active when Ext 1 is being used.
1
Ext 2
1 = Communication monitoring active when Ext 2 is being used.
2
Local
1 = Communication monitoring active when local control is being
used.
3…15
Reserved
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...