284 Parameters
91
Configuration of encoder interface modules.
0000 0000b …
0011 0011b
Status word of digital inputs on FEN-xx modules.
1 = 1
Displays the type of the interface module found in the location
specified by parameter
.
This parameter is read-only.
-
No option
No module detected in the specified slot.
0
No communication
A module has been detected but cannot be communicated
with.
1
Unknown
The module type is unknown.
2
FEN-01
An FEN-01 module has been detected and is active.
16
FEN-31
An FEN-31 module has been detected and is active.
21
Displays the temperature measured through the sensor input
of interface module 1.
Note:
With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
0…1000 °C, or ohm Temperature measured through interface module 1.
-
Validates any changed encoder interface module parameters.
This is needed for any parameter changes in groups 90…93
to take effect.
After refreshing, the value reverts automatically to
Notes:
• Permanent magnet motors only: The drive will perform a
fresh autophasing routine (see page
) at next start if the
motor feedback encoder settings have been changed.
• The parameter cannot be changed while the drive is
running.
Done
Refreshing done.
0
Refresh
Refreshing.
1
Defines the type of the module used as interface module 1.
None
None (communication disabled).
0
FEN-01
FEN-01.
1
FEN-31
FEN-31.
4
Specifies the slot 1 on the control unit of the drive into which
the interface module is installed.
Slot 2
Slot 1
Slot 1.
1
Specifies the type of temperature sensor connected to
interface module 1. Note that the module must also be
activated by parameters
None
None.
0
PTC
PTC. (The unit is ohms.)
1
KTY-84
KTY84. (The unit is selected by parameter
96.16
Unit
selection
.)
2
Defines a filtering time for the temperature measurement
through interface module 1.
1500 ms
0…10000 ms
Filtering time for temperature measurement.
-
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...