132 Parameters
Defines the real maximum value of the signal (selected by
parameter
) that corresponds to the
maximum required AO2 output value (defined by parameter
). See parameter
100.0
-32768.0 …
32767.0
Real signal value corresponding to maximum AO2 output
value.
1 = 1
Defines the minimum output value for analog output AO2.
See also drawing at parameter
0.000 mA
0.000 … 22.000 mA Minimum AO2 output value.
1000 = 1 mA
Defines the maximum output value for analog output AO2.
See also drawing at parameter
20.000 mA
0.000 … 22.000 mA Maximum AO2 output value.
1000 = 1 mA
Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In
, select
. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (
…
)
0.00
-327.68 … 327.67
Storage parameter for AO1.
100 = 1
Storage parameter for controlling analog output AO2 eg.
through fieldbus.
In
, select
. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (
…
)
0.00
-327.68 … 327.67
Storage parameter for AO2.
100 = 1
16
Selection of local and external control location sources and
operating modes.
See also section
Operating modes of the drive
(page
22
).
Displays the operating mode currently used.
See parameters
.
This parameter is read-only.
-
Zero
None.
1
Speed
Speed control (in Vector motor control mode).
2
Torque
Torque control (in Vector motor control mode).
3
Min
The torque selector is comparing the output of the speed
controller (
Torque reference speed control
) and torque
reference (
) and the smaller of the
two is used.
4
Max
The torque selector is comparing the output of the speed
controller (
Torque reference speed control
) and torque
reference (
) and the greater of the
two is used.
5
Add
The speed controller output is added to the torque reference.
6
Scalar (Hz)
Frequency control in scalar motor control mode.
10
Scalar (rpm)
Speed control in scalar motor control mode.
11
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...