12.2.2.3
Function block
SCSWI
BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS*
EXE_OP
EXE_CL
SELECTED
START_SY
POSITION
OPENPOS
CLOSEPOS
CMD_BLK
L_CAUSE
POS_INTR
XOUT
IEC09000087_1_en.vsd
IEC09000087 V1 EN
Figure 169:
SCSWI function block
12.2.2.4
Signals
Table 214:
SCSWI Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
2
Operator place selection
L_SEL
BOOLEAN
0
Select signal from local panel
L_OPEN
BOOLEAN
0
Open signal from local panel
L_CLOSE
BOOLEAN
0
Close signal from local panel
AU_OPEN
BOOLEAN
0
Used for local automation function
AU_CLOSE
BOOLEAN
0
Used for local automation function
BL_CMD
BOOLEAN
0
Steady signal for block of the command
RES_EXT
BOOLEAN
0
Reservation is made externally
SY_INPRO
BOOLEAN
0
Synchronizing function in progress
SYNC_OK
BOOLEAN
0
Closing is permitted at set to true by the
synchrocheck
EN_OPEN
BOOLEAN
0
Enables open operation
EN_CLOSE
BOOLEAN
0
Enables close operation
XPOS
GROUP
SIGNAL
-
Group signal from XCBR/XSWI
Table 215:
SCSWI Output signals
Name
Type
Description
EXE_OP
BOOLEAN
Execute command for open direction
EXE_CL
BOOLEAN
Execute command for close direction
SELECTED
BOOLEAN
Select conditions are fulfilled
START_SY
BOOLEAN
Starts the synchronizing function
POSITION
INTEGER
Position indication
OPENPOS
BOOLEAN
Open position indication
Table continues on next page
1MRK 502 048-UEN A
Section 12
Control
339
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...