3200 Series
82 Part No HA028651 Issue 7.0 Apr-09
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
A2.HYS
Alarm 2 Hysteresis
68
A3.HYS
Alarm 3 Hysteresis
69
A4.HYS
Alarm 4 Hysteresis
71
StAt
Instrument Status. This is a bitmap:
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B4 – Auto/Manual Status
B5 – Sensor Break Status
B6 – Loop Break Status
B7 – CT Low load current alarm status
B8 – CT High leakage current alarm status
B9 – Program End
B10 – PV Over-range (by > 5% of span)
B11 – CT Overcurrent alarm status
B12 – New Alarm Status
B13 – Timer/Ramp Running
B14 – Remote (comms) SP Fail
B15 – Auto-tune Status
In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.
75
-
Inverted Instrument Status. This is an inverted (bitwise) version of the preceding parameter and is provided so that
scrolling messages can be triggered when a condition is not active. Bit mappings are as the “Instrument Status”,
Modbus address 75
76
LL.AMP
Load Leakage Current
79
LD.AMP
Load ON Current
80
A3.---
Alarm 3 Threshold
81
A4.---
Alarm 4 Threshold
82
LBT
Loop Break Time
83
F.OP
Forced manual output value
84
F.MOD
Forced manual output mode
0 – None
1 - Step
2 - Last
85
HYST.H
Ch1 On/Off Hysteresis in Eng Units
86
Di.IP
Digital Inputs Status. This is a bitmap:
B0 – Logic input 1A
B1 – Logic input LA
B2 – Logic input LB
B7 – Power has failed since last alarm acknowledge
A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not
configured as inputs.
87
HYST.C
Ch2 On/Off Hysteresis in Eng Units
88
FILT.T
Input Filter Time
101
RC.FT
Filter time constant for the rate of change alarm.
102
RC.PV
Calculated rate of change of the temperature or process variable in engineering units per minute.
103
Home Home
Display.
0 – Standard PV and SP display
1 – PV and Output Power display
2 – PV and Time remaining display
3 – PV and Timer elapsed time display
4 – PV and Alarm 1 setpoint
5 – PV and Load Current
6 – PV only
7 – PV and Composite SP/Time remaining
8 – Target setpoint
9 – No PV
10 – PV is not displayed when controller in Standby
106