3200 Series
Part No HA028651 Issue 7.0 Apr-09 83
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
-
Instrument version number. Should be read as a hexadecimal number, for example a value of 0111 hex is instrument
V1.11
107
SP.HI
Setpoint High Limit
111
SP.LO
Setpoint Low Limit
112
-
Instrument type code.
122
ADDR
Instrument Comms Address
131
PV.OFS PV
Offset
141
C.Adj
Calibration Adjust
146
IM Instrument
Mode
0 – Operating mode - all algorithms and I/O are active
1 – Standby - control outputs are off
2 – Config Mode - all outputs are inactive
199
MV.IN
Input value in millivolts
202
PV.CM
Comms PV Value. This may be used to write to the Process Variable (temperature) parameter over Modbus when a
linearisation type of ‘Comms’ is selected, allowing the instrument to control to externally derived values.
If sensor break is turned on, it is necessary to write to this variable once every 5 seconds. Otherwise a sensor break
alarm will be triggered as a failsafe. If this is not required, turn sensor break off.
203
CJC.IN CJC
Temperature
215
SBR
Sensor Break Status (0 = Off, 1 = Active)
258
NEW.AL
New Alarm Status (0 = Off, 1 = Active)
260
LBR
Loop Break (0 = Off, 1 = Active)
263
A.TUNE
Auto-tune Enable (0 = Off, 1 = Enabled)
270
A-M
Mode of the Loop (0 = Auto, 1 = Manual)
273
Ac.All
Acknowledge all alarms (1 = Acknowledge
274
L-R
Local Remote (Comms) Setpoint Select
276
Remote setpoint in percent
277
REM.HI
Remote input high scalar – sets high range for setpoint input, corresponding to 20mA or 10V depending on the
input type.
278
REM.LO
Remote input low scalar – sets low range for setpoint input, corresponding to 4mA or 0V depending on the input
type.
279
ROP.HI
Sets the high range limit for the retransmitted setpoint. Allows a subset of the setpoint range to be retransmitted,
and also allows the 3208/3204 setpoint range meter to display a range indication other than full scale. By default
this is set to the setpoint high limit.
280
ROP.LO
Sets the low range limit for the retransmitted setpoint. Allows a subset of the setpoint range to be retransmitted,
and also allows the 3208/3204 setpoint range meter to display a range indication other than full scale. By default
this is set to the setpoint low limit.
281
A1.STS
Alarm 1 Status (0 = Off, 1 = Active)
294
A2.STS
Alarm 2 Status (0 = Off, 1 = Active)
295
A3.STS
Alarm 3 Status (0 = Off, 1 = Active)
296
A4.STS
Alarm 4 Status (0 = Off, 1 = Active)
297
LD.ALM
Low Load Current Threshold
304
LK.ALM
High Leakage Current Alarm (0 = Off, 1 = Active)
305
HC.ALM
Over Current Alarm Threshold
306
LOAD.A
Load Alarm Status (0 = Off, 1 = Active)
307
LEAK.A
Leak alarm Status.
308
HILC.A
Over Current alarm Status (0 = Off, 1 = Active)
309
REC.NO
Recipe to Recall
313
StOrE
Recipe to Save
314
TM.CFG
Timer type configuration
0 – No Timer
1 – Dwell Timer
2 – Delay Timer
3 – Soft Start Timer
10 – Programmer (Programmer Option only)
320
TM.RES Timer
Resolution
0 – Hours:Mins
321