4-290
Flow-X─ Function Reference
Flow-X General functions - fxSolartron_Liquid_M
fxSolartron_Liquid_M
The function calculates the density from a frequency input signal provided by a Solartron 7835, 7845,
7846 or 7847 liquid densitometer and corrects it for temperature, pressure and velocity of sound
effects using metric units.
The function requires that the calibration constants are based on the following units:
Temperature
°
C
Pressure
bar
Density
kg/m3
Compliance
The calculations are in accordance with documents:
78355010 'Solartron 7835, 7845, 7846 & 7847 Advanced Liquid Density Transducer
Manual', 2001
78355080, Rev. C, 'Micro Motion 7835, 7845, 7846 & 7847 Liquid Density Transducer',
October 2007
Function inputs and outputs
Function inputs
Remark
EU
Range
Default
Name
Optional tag name, tag
description and tag group
Periodic time
In microseconds
Equals 1000 divided by the
frequency in [Hz]
s
0..1e6
0
Line temperature
Used when temperature
correction is enabled
°C
-273.15..+500
0
Line pressure
Used when pressure correction
is enabled
bar(g)
0..200
0
Temperature correction
0: Disabled
1: Enabled
-
1
Pressure correction
0: Disabled
1: Enabled
-
1
VOS correction
0: Disabled
1: Based on Kr / Kj Constants
Solartron manual edition
1985
2: Based on VOS value
Solartron manual edition
1996 and later
-
2
Reference temperature
Used when temperature
correction is enabled
°C
0..100
20
Reference pressure
Used when pressure correction
is enabled
bar(g)
0..100
0
K0
Constant from calibration
certificate
-
-1e9..1e9
1.7418E2
K1
Constant from calibration
certificate
-
-1e9..1e9
-1.10493e0
K2
Constant from calibration
certificate
-
-1e9..1e9
3.703268e-4
K18
Constant from calibration
certificate
-
-1e9..1e9
-6.415e-4
K19
Constant from calibration
certificate
-
-1e9..1e9
-5.674e-1
K20A
Constant from calibration
certificate
-
-1e9..1e9
2.888e-4
K20B
Constant from calibration
-
-1e9..1e9
-5.581e-6
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...