Flow-X─ Function Reference
Flow-X IO Functions - fxSetFrequencyOutput
fxSetFrequencyOutput
This function starts a programmed frequency on the digital pin, set by fxFrequencyOutput. In case of a
dual pulse via frequency out, here the phase shift between the pins can be configured.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Module
Not used, set to -1
-1..16
-1
Index
Index of the frequency output
1..4
Frequency
Output frequency (Hz)
Hz
0.01..
10000
Duty cycle
Duty cycle
%
0..100
Enabled
Enables (<>0) or disables (0) the
output signal.
Phase shift
Phase shift between dual pulse
channel A and B expressed as the
ratio of the time delay between
the last A and B and the time
between two A pulses. A typical
phase difference is 90°
corresponding to a value of 0.25.
The shift is limited to [0°..180°).
0..0.5
0
Function outputs
Remark
SW tag
Alarm
EU
Fallback
Status
0: Normal
1: Input argument out of range or
conflict
STS
FIOOR
-
1
Actual frequency
Actual frequency, which can deviate
from the programmed frequency
because of hardware limitations.
ACTFREQ
Hz
0
Actual duty cycle
ACTDC
%
0
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...