Flexible automation concepts
10.2 Configuration control (option handling)
Automation system
206
System Manual, 12/2017, A5E03461182-AE
Procedure
To set up the configuration control, follow these steps in the order given:
Table 10- 1 Procedure for commissioning the SIMATIC S7-1500
Step
Procedure
See...
1
Enable configuration control in STEP 7
Section Configuring (Page 206)
2
Create control data record
Section Creating the control data record
(Page 208)
3
Transfer control data record
Section Transferring the control data
record in the startup program of the CPU
(Page 217)
Block library "OH_S71x00_Library"
The block library OH_S71x00_Library
https://support.industry.siemens.com/cs/ww/en/view/29430270
) is available for download
from the Internet. The block library contains data types with the structure of the control data
records for the S7-1500/ET 200MP. You can implement your flexible automation solution
economically with the help of these data types.
10.2.1
Configuring
Requirements
With the S7-1500, configuration control is possible both with centrally inserted modules and
with the ET 200MP distributed I/O system via PROFINET IO.
For S7-1500 automation system:
●
STEP 7 Professional as of Version V13
●
CPU S7-15XX as of firmware version V1.5
●
The startup parameter "Comparison preset to actual configuration" is set to "Startup CPU
even if mismatch" (default setting).
You can find the "Comparison preset to actual configuration" parameter in the Inspector
window of the CPU properties under "General">"Startup".
For ET 200MP distributed I/O system:
●
STEP 7 Professional as of Version V13
●
IM 155-5 PN ST/HF
●
You have assigned the interface module to an IO controller/DP master in STEP 7
●
The startup parameter "Comparison preset to actual module" is set to "Startup CPU even
if mismatch" (default setting).
You can find the "Comparison preset to actual module" parameter in the Inspector
window of the interface module properties in the "Startup" field under "General">"Module
parameters".
Summary of Contents for Simatic S7-1500/ET 200MP
Page 1: ......