Identifier
VM_POSITIVE_REF_CLAMP
Description
Limits applied to the positive frequency reference clamp
Units
Hz
Range of [MIN]
0.00
Range of [MAX]
550.00
VM_POSITIVE_REF_CLAMP[MAX] defines the range of the positive reference clamps,
Maximum Reference Clamp
(01.006) and
M2 Maximum
Reference Clamp
(21.001) , which in turn limits the references.
Note - Parameter 11.045 is not available on M100/M101 and so only the Motor 1 parameter is relevant.
This values are model dependent. See the table below.
Models
Clamp level
M100 - M400
550.00
Commander ID
150.00
Identifier
VM_POWER
Description
Range applied to parameters that either set or display power
Units
kW
Range of [MIN]
-9999.99 to 0.00
Range of [MAX]
0.00 to 9999.99
VM_POWER[MAX] is rating dependent and is chosen to allow for the maximum power that can be output by the drive with maximum a.c. output
voltage, at maximum controlled current and unity power factor.
VM_POWER[MAX] = √3 x VM_AC_VOLTAGE[MAX] x VM_DRIVE_CURRENT[MAX] / 1000
VM_POWER[MIN] = -VM_POWER[MAX]
Identifier
VM_RATED_CURRENT
Description
Range applied to rated current parameters
Units
A
Range of [MIN]
0.00
Range of [MAX]
0.00 to 9999.99
VM_RATED_CURRENT [MAX] =
Maximum Rated Current
(11.060) and is dependent on the drive rating.
VM_RATED_CURRENT [MIN] = 0.00
Identifier
VM_SPEED_FREQ_REF
Description
Range applied to the frequency reference parameters
Units
Hz
Range of [MIN]
-550.00 to 0.00
Range of [MAX]
0.00 to 550.00
This variable minimum/maximum is applied throughout the frequency and speed reference system so that the references can vary in the range from the
minimum to maximum clamps.
Negative
Reference Clamp
Enable
(01.008)
VM_SPEED_FREQ_REF[MAX] if
Select
Motor 2 Parameters
(11.045) = 0
VM_SPEED_FREQ_REF[MAX] if
Select
Motor 2 Parameters
(11.045) = 1
0
Maximum Reference Clamp
(01.006)
M2 Maximum Reference Clamp
(21.001)
1
Maximum Reference Clamp
(01.006) or
|
Minimum Reference Clamp
(01.007)|
whichever the larger
M2 Maximum Reference Clamp
(21.001) or
|M2
Minimum Reference Clamp
(21.002)|
whichever the larger
VM_SPEED_FREQ_REF[MIN] = -VM_SPEED_FREQ_REF[MAX].
Note - Parameter 11.045 is not available on M100/M101 and so only the Motor 1 parameters are relevant.
Identifier
VM_SPEED_FREQ_REF_UNIPOLAR
Description
Unipolar version of VM_SPEED_FREQ_REF
Units
Hz
Range of [MIN]
0.00
Range of [MAX]
0.00 to 550.00
VM_SPEED_FREQ_REF_UNIPOLAR[MAX] = VM_SPEED_FREQ_REF[MAX]
12
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...