This is NOT a full comms compatibility to previous drive generations. Only the following parameters are converted.
Because of the limited number of segments on drives with an LED display, these drives will indicate the parameter value as a decimal value rather than
a binary value.
Modbus Parameter Conversion
(11.099) bits
Effect
0
Frequency parameters:
1.001,1.002,1.003,1.004,1.005,1.006,1.007,1.017,1.021,1.022,
1.023,1.024,1.025,1.026,1.027,1.028,1.029,1.030,1.031,1.032,
1.033,1.034,1.036,1.037,1.038,2.001,3.005,3.006,3.022,3.043,
3.045,5.001,5.006,12.044,12.045,21.001,21.002,21.006 scaled by 10.
1
Source/Destination parameters:
7.010,7.014,7.019,8.021,8.022,8.023,8.024,8.025,8.028,9.004,9.006,
9.010,9.014,9.016,9.020,9.025,9.033,12.003,12.007,12.008,12.009,
12.011,12.023,12.027,12.028,12.029,12.031,14.002,14.003,14.004,14.009,14.016.
Parameter number is converted from 3 to 2 digits (i.e. #1.01 is #1.001)
2
Percentage parameters:
7.001,7.002,7.030,7.031,9.003,12.004,12.005,12.012,12.024,12.025,
12.032,14.001,14.013,14.014,14.019,14.020,14.021,14.022 scaled by 10
3
Motor parameters: 5.008,5.017,5.024,21.008,21.012,21.014 scaled by 10
Examples:
bit 0:
If 01.021 = 1.23Hz, then value read is 12 equivalent of 1.20Hz
If value 123 is written to 01.021 then 01.021 = 12.30Hz
bit 1:
If
Analog Input 1 Destination A
(07.010) = 1.036, then value read is 136.
If value 136 is written to
Analog Input 1 Destination A
(07.010) then
Analog Input 1 Destination A
(07.010) = 1.036.
bit 2:
If
Analog Input 1
(07.001) = 50.0%, then value read is 500.
bit 3:
If
Motor Rated Speed
(05.008) = 1500.0, then value read is 1500.
If value 1500 is written to
Motor Rated Speed
(05.008) then
Motor Rated Speed
(05.008) = 1500.0.
190
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...