It is possible for some trips to cause the motor to stop before the trip is initiated (see
Action On Trip Detection
(10.037)). During the period while the motor is being
stopped before the trip is initiated
Stop Motor
(10.080) is set to one. Once the motor stops
Stop Motor
(10.080) is set back to zero.
Parameter
10.081
Phase Loss
Short description
Indicates that the drive has detected an input phase loss
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
If phase loss or imbalance is detected that would initiate a phase loss trip with sub-trip 0, i.e.
Phase Loss
.000, then
Phase Loss
(10.081) is set to one. Either the
motor will be stopped and the drive tripped or the drive will continue to operate normally until the user stops the motor and the drive trips (see
Action On Trip Detection
(10.037)). In either case
Phase Loss
(10.081) is set to one when the phase loss condition is detected and remains set until the drive trips.
Parameter
10.090
Drive Ready
Short description
Indicates that the drive is ready and a run command is not active
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Drive Ready
(10.090) indicates that the drive is ready and a run command is not active.
Parameter
10.101
Drive Status
Short description
Shows the present status of the drive
Mode
Open
‑
loop
Minimum
0
Maximum
15
Default
Units
Type
8 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, TE, ND, NC, PT, BU
Value
Text
Description
0
inh
Drive is not enabled
1
rdy
Drive is enabled but has not received a Run command
2
Stop
Drive has been stopped, but is still active
4
Run
Drive is running (not seen on LED display on M100 - M300, the
frequency is displayed instead)
5
S.Loss
Supply loss has been detected
6
dEcEl
Drive is decelerating (not seen on LED display on M100 - M300,
the frequency is displayed instead)
7
dc.inj
Drive is applying current injection to the motor
9
Error
Drive has tripped
14
Heat
Current is being applied to the motor to warm it up
15
UU
Drive is in the Under Voltage state
Drive Status
(10.101) shows the present status of the drive. The strings from this parameter are also used by the basic keypad to provide the status display text.
Parameter
10.102
Trip Reset Source
Short description
Indicates whether a trip in the trip log has been reset
Mode
Open
‑
loop
Minimum
0
Maximum
1023
Default
Units
Type
16 Bit Power Down Save
Update Rate
Write on trip
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT, BU
The bits in
Trip Reset Source
(10.102) correspond to each of the trips in the trip log (i.e. bit 0 corresponds to trip 0, bit 1 corresponds to trip 1, etc.). When a trip
occurs, bit 0 is set to one and the other bits corresponding to the trips already in the trip log are shifted left one bit. If the trip is reset then bit 0 is set back to zero,
otherwise if a higher priority trip occurs bit 0 is shifted left by one bit. The result is that each of the bits in
Trip Reset Source
(10.102) show whether trips in the trip log
were reset or moved up the trip log by a higher priority trip.
Parameter
10.103
Trip Time Identifier
Short description
Shows time in milliseconds since the drive powered up when a trip occurred
Mode
Open
‑
loop
Minimum
-2147483648
Maximum
2147483647
Default
Units
ms
Type
32 Bit Volatile
Update Rate
Write on trip
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
When a trip occurs the time in milliseconds since the drive powered up is stored in
Trip Time Identifier
(10.103). The time rolls-over when it reaches 2
32
- 1, but if the
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
167
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...