Parameter
05.002
Output Voltage
Short description
Displays the r.m.s. line to line voltage at the a.c. terminals of the drive
Mode
Open
‑
loop
Minimum
−VM_AC_VOLTAGE
Maximum
VM_AC_VOLTAGE
Default
Units
V
Type
16 Bit Volatile
Update Rate
16ms
Display Format
Standard
Decimal Places
0
Coding
RO, FI, VM, ND, NC, PT
The
Output Voltage
(05.002) is the r.m.s line to line voltage at the a.c. terminals of the drive.
Parameter
05.003
Output Power
Short description
Displays the power flowing via the a.c. terminals of the drive
Mode
Open
‑
loop
Minimum
−VM_POWER
Maximum
VM_POWER
Default
Units
kW
Type
32 Bit Volatile
Update Rate
16ms
Display Format
Standard
Decimal Places
2
Coding
RO, FI, VM, ND, NC, PT
The
Output Power
(05.003) is the power flowing via the a.c. terminals of the drive. The power is derived as the dot product of the output voltage and current
vectors, and so this is correct even if the motor parameters are incorrect and the motor model does not align the reference frame with the flux axis of the
motor. A positive value of power indicates power flowing from the drive to the motor.
The maximum power is VM_POWER[MAX] = √3 x VM_AC_VOLTAGE[MAX] x
Full Scale Current Kc
(11.061) / 1000
Parameter
05.004
Motor Rpm
Short description
Displays the Final Demand Reference in units of rpm
Mode
Open
‑
loop
Minimum
-33000
Maximum
33000
Default
Units
rpm
Type
32 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, FI, ND, NC, PT
Motor Rpm
(05.004) = 60 x Frequency / Pole pairs
where
Pole pairs = the numeric value of
Number Of Motor Poles
(i.e. 3 for a 6 pole motor)
The frequency used to derive the
Motor Rpm
(05.004) is the
Final Demand Reference
(03.001). The maximum and minimum values allow for a 10% over-
shoot of the speed.
Parameter
05.005
D.c. Link Voltage
Short description
Displays the voltage across the d.c. link of the drive
Mode
Open
‑
loop
Minimum
−VM_DC_VOLTAGE
Maximum
VM_DC_VOLTAGE
Default
Units
V
Type
16 Bit Volatile
Update Rate
16ms
Display Format
Standard
Decimal Places
0
Coding
RO, FI, VM, ND, NC, PT
D.c. Link Voltage
(05.005) gives the voltage across the d.c. link of the drive.
Parameter
05.006
Motor Rated Frequency
Short description
Set to the rated frequency of the motor
Mode
Open
‑
loop
Minimum
0.00
Maximum
550.00
Default
See exceptions below
Units
Hz
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
Region
Default Value
50Hz
50.00
60Hz
60.00
Motor Rated Frequency
(05.006) and
Motor Rated Voltage
(05.009) define the frequency to voltage characteristic applied to the motor. See
Open-
loop Voltage Mode
(05.014) for more details.
Motor Rated Frequency
(05.006),
Motor Rated Speed
(05.008) and
Number Of Motor Poles
(05.011) are used to
calculate the rated slip of the motor for slip compensation.
Rated slip
(Hz) =
Motor Rated Frequency
(05.006) - (Pole pairs x
Motor Rated Speed
(05.008) / 60)
where
Pole pairs = the numeric value of
Number Of Motor Poles
(05.011) (i.e. 3 for a 6 pole motor)
64
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...