CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-83
3
DeaV1
SPS
SYNC # V1 BELOW MAX operand, which
indicates that V1 is below the DeaVal1
setting
R
stVal
BOOLEAN
ST SYNC # V1 BELOW MAX
R
LivV2
SPS
SYNC # V2 ABOVE MIN operand, which
indicates that V1 is above the LivVal2
setting
R
stVal
BOOLEAN
ST SYNC # V2 ABOVE MIN
R
DeaV2
SPS
SYNC # V2 BELOW MAX operand, which
indicates that V2 is below the DeaVal1
setting
R
stVal
BOOLEAN
ST SYNC # V2 BELOW MAX
R
LivDea
SPS
SYNC # DEAD S OP operand, which
indicates that live/dead conditions have
been met
R
stVal
BOOLEAN
ST SYNC # DEAD S OP
R
LivDeaDpo
SPS
SYNC # DEAD S DPO operand, which
indicates that live/dead conditions have not
been met
R
stVal
BOOLEAN
ST SYNC # DEAD S DPO
R
LivLiv
SPS
SYNC # SYNC OP operand, which indicates
that both sources are live, and that angle,
frequency and voltage difference and
range conditions have been met
R
stVal
BOOLEAN
ST SYNC # SYNC OP
R
LivLivDpo
SPS
SYNC # SYNC DPO operand, which indicates
that one or both sources are not live, or that
angle, frequency and voltage difference
and range conditions have been met
R
stVal
BOOLEAN
ST SYNC # SYNC DPO
R
DifVClc
MV
SYNCHROCHECK # DELTA VOLT, in primary
volts
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SYNCHROCHECK 1 DELTA VOLT
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
SYNCHROCHECK # DELTA VOLT,
deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
29, the code for volts
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF SynChkRSYN#.DifVClc.db
R/W/C
zeroDb
INT32U
CF
R
DifHzClc
MV
SYNCHROCHECK # DELTA FREQ, in Hz
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SYNCHROCHECK # DELTA FREQ
multiplied by 100
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
SYNCHROCHECK # DELTA FREQ
multiplied by 100, on deadband
exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
33, the code for hertz (1/s)
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF SynChkRSYN#.DifHzClc.db
R/W/C
zeroDb
INT32U
CF
0
R
LNName:
SynChkRSYN#
LDevice inst:
Ctrl
UR element:
Synchrocheck element # (ANSI 25)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...