3-84
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.6 Thermal overload (ThmOvl)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, N60, T35,
T60.
Table 3-83: Thermal overload data objects
3.5.3.7 Three pole autoreclose (Rec3p)
This element is instantiated in the following products: D30, F35, F60, L30.
Table 3-84: Three pole autoreclose data objects
DifAngClc
MV
SYNCHROCHECK # DELTA PHASE, in
degrees
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SYNCHROCHECK # DELTA PHASE
multiplied by 10
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
SYNCHROCHECK # DELTA PHASE
multiplied by 10, on deadband
exception
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
9 is the code for degrees
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF SynChkRSYN#.DifAngClc.db
R/W/C
zeroDb
INT32U
CF
0
R
BlkRef1
ORG
SYNCHK# BLOCK setting.
R
setSrcRef
ObjectReference
SP SYNCHK# BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
ThmOvlPTTR#
LDevice inst:
Ctrl
UR element:
THERMAL OVERLOAD PROTECTION # element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
THERMAL PROT # OP operand
R
general
BOOLEAN
ST THERMAL PROT # OP
R
Str
ACD
THERMAL PROT # PKP operand
R
general
BOOLEAN
ST THERMAL PROT # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
InRef2
ORG
THERMAL PROT # RESET setting
R
setSrcRef
ObjectReference
SP THERMAL PROT # RESET
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
THERMAL PROT # BLOCK setting
R
setSrcRef
ObjectReference
SP THERMAL PROT # BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
Rec3pRREC#
LDevice inst:
Ctrl
UR element:
Autoreclose element # functions
data obj. data attribute
Type
FC UR Name
Description
R/W/C
ShotCnt
INS
AUTORECLOSE# SHOT COUNT actual value
R
stVal
INT32
ST AUTORECLOSE# SHOT COUNT
R
AutoRecSt
ENS
Autoreclosing status
R
stVal
ENUMERATED
ST
R
Ena1
SPS
AR# ENABLED operand
R
stVal
BOOLEAN
ST AR# ENABLED
R
ArRip
SPS
AR# RIP operand
R
stVal
BOOLEAN
ST AR# RIP
R
LNName:
SynChkRSYN#
LDevice inst:
Ctrl
UR element:
Synchrocheck element # (ANSI 25)
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...