3-90
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-92: Breaker control data objects
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
Bkr0XCBR#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
EEHealth
ENS
Breaker health, value is 2 (yellow) when
breaker is out of service, 3 (red) when
breaker trouble is detected and breaker is
not out of service
R
stVal
BOOLEAN
ST
2 when BREAKER # OOS is On, otherwise 3
when operand BREAKER # TROUBLE is On,
otherwise 1
R
Loc
SPS
Value of operand selected by setting XCBR#
ST.LOC OPERAND
R
stVal
BOOLEAN
ST
Value of operand selected by setting XCBR#
ST.LOC OPERAND
R
OpCnt
INS
Breaker operations counter
R
stVal
INT32
ST
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
OpOpn
ACT
BREAKER # OFF CMD (3-phase trip),
BREAKER # TRIP A, BREAKER # TRIP B and
BREAKER # TRIP C operands
R
general
BOOLEAN
ST BREAKER # OFF CMD
R
phsA
BOOLEAN
ST BREAKER # TRIP A
R
phsB
BOOLEAN
ST BREAKER # TRIP B
R
phsC
BOOLEAN
ST BREAKER # TRIP C
R
OpCls
ACT
BREAKER # ON CMD (close) operand
R
general
BOOLEAN
ST BREAKER # ON CMD
R
BadSt1
SPS
BREAKER # BAD STATUS operand
R
stVal
BOOLEAN
ST BREAKER # BAD STATUS
R
ClsSt1
SPS
BREAKER # CLOSED operand
R
stVal
BOOLEAN
ST BREAKER # CLOSED
R
OpnSt1
SPS
BREAKER # OPEN operand
R
stVal
BOOLEAN
ST BREAKER # OPEN
R
Dsc
SPS
BREAKER # DISCREP operand, which is
breaker pole discrepancy status
R
stVal
BOOLEAN
ST BREAKER # DISCREP
R
Alm
SPS
BREAKER # TROUBLE operand, which is
breaker pole discrepancy, bad-status, or
BREAKER # EXT ALARM
R
stVal
BOOLEAN
ST BREAKER # TROUBLE
R
MnlCls
SPS
BREAKER # MNL CLS operand
R
stVal
BOOLEAN
ST BREAKER # MNL CLS
R
AnyPoleOp
n
SPS
BREAKER # ANY P OPEN operand
R
stVal
BOOLEAN
ST BREAKER # ANY P OPEN
R
OnePoleOp
n
SPS
BREAKER # ONE P OPEN operand
R
stVal
BOOLEAN
ST BREAKER # ONE P OPEN
R
OutOfSrv
SPS
BREAKER # OOS operand
R
stVal
BOOLEAN
ST BREAKER # OOS
R
LNName:
BkrCILO#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...