3-92
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-93: Breaker control data objects
InRef4
ORG
BREAKER # BLK CLOSE setting
R
setSrcRef
ObjectReference
SP BREAKER # BLK CLOSE
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef8
ORG
XCBR# SYNCCHECK CLS setting
R
setSrcRef
ObjectReference
SP XCBR# SYNCCHECK CLS
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef5
ORG
BREAKER # EXT ALARM setting
R
setSrcRef
ObjectReference
SP BREAKER # EXT ALARM
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef6
ORG
BREAKER # OUT OF SV (out-of-service)
setting.
R
setSrcRef
ObjectReference
SP BREAKER # OUT OF SV
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef7
ORG
XCBR# ST.LOC OPERAND (local control)
setting.
R
setSrcRef
ObjectReference
SP XCBR# ST.LOC OPERAND
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
Bkr
Θ
XCBR#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Loc
SPS
Value of operand selected by setting XCBR#
ST.LOC OPERAND
R
stVal
BOOLEAN
ST Bkr0XCBR#.Loc.stVal
R
OpCnt
INS
Phase
ψ
breaker operations counter
R
stVal
INT32
ST
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
BadSt1
SPS
BREAKER #
ψ
BAD ST operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
BAD ST
R
ClsSt1
SPS
BREAKER #
ψ
CLSD operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
CLSD
R
OpnSt1
SPS
BREAKER #
ψ
OPEN operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
OPEN
R
IntermSt1
SPS
BREAKER #
ψ
INTERM operand
R
stVal
BOOLEAN
ST BREAKER #
ψ
INTERM
R
Pos
DPC
Breaker
φψ
position status
R
stVal
CODED ENUM
ST
R
ctlModel
CtlModels
CF
0, the code for status-only
R
BlkOpn
SPC
Breaker open commands blocked from all
sources including protection
R
stVal
BOOLEAN
ST Bkr0XCBR#.BlkOpn.stVal
R
ctlModel
CtlModels
CF
0, the code for status-only
R
BlkCls
SPC
Breaker close commands blocked from all
sources including protection
R
stVal
BOOLEAN
ST Bkr0XCBR#.BlkCls.stVal
R
ctlModel
CtlModels
CF
0, the code for status-only
R
InRef1
ORG
BREAKER #
φ
A/3P CLSD setting” if
Θ
=”1”,
“BREAKER #
φ
B CLSD setting” if
Θ
=”2”, or
“BREAKER #
φ
C CLSD setting” if
Θ
=”3
R
LNName:
Bkr0XCBR#
LDevice inst:
System
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...