Function
Details
[Source] > Frequency (f) (from current) > [Equipment] | L1
[Hz]
The controller outputs the L1 frequency (based on the current
measurement).
[Source] > Frequency (f) (from current) > [Equipment] | L2
[Hz]
The controller outputs the L2 frequency (based on the current
measurement).
[Source] > Frequency (f) (from current) > [Equipment] | L3
[Hz]
The controller outputs the L3 frequency (based on the current
measurement).
[Source] > Frequency (f) (from current) > [Equipment] |
Min. [Hz]
The controller outputs the frequency of the phase with the lowest
frequency (based on the current measurement).
[Source] > Frequency (f) (from current) > [Equipment] |
Max. [Hz]
The controller outputs the frequency of the phase with the highest
frequency (based on the current measurement).
Table 3.9
[Source] current analogue output functions
Function
Details
[Source] > Current (I) > [Equipment] | L1 [A]
The controller outputs the L1 current from the source.
[Source] > Current (I) > [Equipment] | L2 [A]
The controller outputs the L2 current from the source.
[Source] > Current (I) > [Equipment] | L3 [A]
The controller outputs the L3 current from the source.
[Source] > Current (I) > [Equipment] | N [A]
The controller outputs the N current from the source, relative to the
star point.
[Source] > Current (I) > [Equipment] | Positive sequence [A]
The controller outputs the magnitude of the positive sequence
current.
[Source] > Current (I) > [Equipment] | Negative sequence [A]
The controller outputs the magnitude of the negative sequence
current.
[Source] > Current (I) > [Equipment] | Zero sequence [A]
The controller outputs the magnitude of the zero sequence current
from the source.
[Source] > Current (I) > [Equipment] | Min. [A]
The controller outputs the lowest phase current.
[Source] > Current (I) > [Equipment] | Max. [A]
The controller outputs the highest phase current.
[Source] > Current (I) > [Equipment] | Unbalanced nominal
[A]
The controller outputs the unbalanced current from the source,
calculated using the nominal method.
[Source] > Current (I) > [Equipment] | Unbalanced average
[A]
The controller outputs the unbalanced current from the source,
calculated using the average method.
Table 3.10
[Source] current - ACM3.2 analogue output functions
Function
Details
[Source] > Current (I) - ACM3.2 > [Equipment] | L1 (Consumer
side) [A]
The controller outputs the L1 current from the consumer side.
[Source] > Current (I) - ACM3.2 > [Equipment] | L2 (Consumer
side) [A]
The controller outputs the L2 current from the consumer side.
[Source] > Current (I) - ACM3.2 > [Equipment] | L3 (Consumer
side) [A]
The controller outputs the L3 current from the consumer side.
[Source] > Current (I) - ACM3.2 > [Equipment] | Min (Consumer
side) [A]
The controller outputs the lowest phase current from the
consumer side.
[Source] > Current (I) - ACM3.2 > [Equipment] | Max (Consumer
side) [A]
The controller outputs the highest phase current from the
consumer side.
[Source] > Current (I) - ACM3.2 > [Equipment] | L1 (Neutral
side) [A]
The controller outputs the L1 current from the neutral side.
DESIGNER'S HANDBOOK 4189340911K UK
Page 56 of 521