Chapter 8: Using the Command Line Interface
206
Inlet Sensor Threshold Information
This command syntax shows the specified inlet sensor's
threshold-related information.
#
show sensor inlet <n> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor inlet <n> <sensor type>
details
Variables:
<n> is the number of the inlet whose sensors you want to query. For
a single-inlet PDU, <n> is always the number 1.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Displayed information:
Without the parameter "details," only the reading, state, threshold,
deassertion hysteresis and assertion timeout settings of the specified
inlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including resolution and range.
If the requested sensor type is not supported, the "Sensor is not
available" message is displayed.