Chapter 8: Using the Command Line Interface
291
Setting the Inlet's Lower Critical Threshold
This command syntax configures the Lower Critical threshold of an inlet.
config:#
sensor inlet <n> <sensor type> lowerCritical <option>
Variables:
<n> is the number of the inlet that you want to configure. For a
single-inlet PDU, <n> is always the number 1.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
peakCurrent Peak
current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
lineFrequency
Line frequency sensor
residualCurrent
Residual current sensor
phaseAngle
Inlet phase angle sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the lower critical threshold for the
specified inlet sensor.
disable
Disables the lower critical threshold for the
specified inlet sensor.
A numeric
value
Sets a value for the lower critical threshold of the
specified inlet sensor and enables this threshold
at the same time.