Chapter 8: Using the Command Line Interface
298
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the lower critical threshold for the
specified inlet pole sensor.
disable
Disables the lower critical threshold for the
specified inlet pole sensor.
A numeric
value
Sets a value for the lower critical threshold of the
specified inlet pole sensor and enables this
threshold at the same time.
Setting the Lower Warning Threshold for an Inlet Pole
This command syntax configures the Lower Warning threshold of an inlet
pole.
config:#
sensor inletpole <n> <p> <sensor type> lowerWarning <option>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor