Chapter 8: Using the Command Line Interface
316
Note: If you are performing this command over a USB connection,
re-connect the USB cable after the reset is completed, or the CLI
communications are lost.
Resetting Active Energy Readings
You can reset either one active energy sensor or all active energy
sensors at at time to restart the energy accumulation process. Only
users with the 'Admin' role assigned can reset active energy readings.
To reset all active energy readings of the PXE:
#
reset activeEnergy pdu
-- OR --
#
reset activeEnergy pdu /y
To reset one inlet's active energy readings:
#
reset activeEnergy inlet <n>
-- OR --
#
reset activeEnergy inlet <n> /y
If you entered the command without "/y", a message appears prompting
you to confirm the operation. Type y to confirm the reset or n to abort it.
Variables:
<n> is the inlet number. For a single-inlet PDU, the number is always
1.
Resetting to Factory Defaults
The following commands restore all settings of the PXE device to factory
defaults.
To reset PXE settings after login, use either command:
#
reset factorydefaults
-- OR --
#
reset factorydefaults
/y
To reset PXE settings before login:
Username:
factorydefaults
See
Using the CLI Command
(on page 328) for details.