Chapter 5 Instruction Specifications
5-101
Item number
Control instructions-2
Name
Scan conditional end
Ladder format
Condition code
Processing time (
µ
s)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
CEND (s)
DER
ERR
SD
V
C
Upper case :
z
z
z
z
z
5
Conditions
Instruction format
Number of steps
do not meet
Condition
Steps
Lower case :
CEND (s)
2
707
Conditions meet
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC
DX DY
DR,
DM
C
o
nstant
Other
s
Scan end condition
{
{
{
Function
•
If the scan end condition (s) is on, the execution of this instruction returns to the head of the scan program and executes the
program.
•
If (s) is off, the next instruction is executed.
•
This instruction can only be used in normal scan programs, and can be used as many times as desired.
•
This instruction can specify a startup condition. In this case, if the startup condition and (s) are both on, this instruction is
executed.
Notes
•
The CEND instruction is checked prior to the execution, and if there is an error, the following error codes are set in the
special internal output WRF001. Also, the CPU error code '34' is set to special internal output WRF000.
CPU error code
Special internal output
Error code
Error description
34
WRF001
H0023
The CEND instruction is found after the END
instruction.
Instruction for use
CEND (R000)
CEND (R001)
END
Program head
Normal scan program
Normal scan program
Normal scan program
When R000 is on, to
program head
When R000 is off, the next
instruction is executed.
When R001 is on, to
program
When R001 is off, the next
instruction is executed.
CE
ND (s
)
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...