Chapter 6 I/O Specifications
6-1
Chapter 6
I/O Specifications
Table 6.1 lists the input/output classifications and input/output point types that can be used with the MICRO-EH
Table 6.1 Usable I/O classifications and point types
10-point
type
14-point
type
23-point
type
28-point
type
Ite
m
Function
S
ym
bol
Siz
e
10/
16
Name
Number of
points
Number of
points
Number of
points
Number of
points
1
External I/O
X
B
10 Bit external input
6 points
8 points
13 points
16 points
WX
W
16 Word external input
1 word
1 word
1 word
2 words
DX
D
16 Double-word external input
Y
B
10 Bit external output
4 points
6 points
10 points
12 points
WY
W
16 Word external output
1 word
1 word
1 word
1 word
DY
D
16 Double-word external output
Analog input
WX
W
16 Analog input
-
-
2 words
-
Analog output
WY
W
16 Analog output
-
-
1 word
-
Counter input
X
B
10 High-speed counter input
3 points
4 points
4 points
4 points
Interrupt input
X
B
10 Interrupt input
total
total
total
total
Counter
output
Y
B
10 High-speed counter synchronized
output
3 points
4 points
4 points
4 points
Ex
tern
al I/O
*
Pulse/PWM
output
Y
B
10 Pulse output
PWM output
3 point
4 points
4 point
4 points
2
Bit
R
B
16 Bit internal output
1984 points
R
B
16 Bit special internal output
64 points
Word
WR
W
16 Word internal output
4096 words
DR
D
16 Double-word internal output
WR
W
16 Word special internal output
512 words
DR
D
16 D.-word special internal output
Sharing of
M
B
16 Bit internal output
16384 points
bit / word
WM
W
16 Word internal output
1024 words
In
tern
al I/O
DM
D
16 Double-word internal output
3
Edge detection DIF
B
10 Rising edge
512 points
DFN
B
10 Falling edge
512 points
Master control MCS
B
10 Master control set
50 points
MCR
B
10 Master control reset
Timer counter
TD
B
10 On delay timer
SS
B
10 Single-shot timer
CU
B
10 Up counter
CTU
B
10 Up-down counter up input
CTD
B
10 Up-down counter down input
Oth
ers
CL
B
10 Clear progress value
Timer 256 points (0.01 s timer has only 0 to 63)
Counter 256 points (The same area as the timer is used.)
(The same timer counter number cannot be used more
than once.)
*: The external I/O, counter I/O, interrupt input, pulse/PWM outputs use the same area by specifying the operation I/O
operation mode (WRF070). See Chapter 8 for further information.
Note: The MICRO-EH does not support CPU link area (L/WL).
Note: B and W in the Size column represent bit and word (16 bits), respectively.
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...