Chapter 5 Instruction Specifications
5-141
Item number
FUN instructions-15
Name
Pulse frequency output setting changes
Ladder format
Condition code
Processing time (
µ
s)
Remark
R7F4
R7F3
R7F2
R7F1
R7F0
Average Maximum
FUN 150 (s)
DER
ERR
SD
V
C
↕
z
z
z
z
Instruction format
Number of steps
217
Condition
Steps
FUN 150 (s)
—
3
Bit
Word
Double word
Usable I/O
X
Y
R,
M
TD, SS,
CU, CT
WX WY
WR,
WM TC DX DY
DR,
DM
C
o
nstant
Other
s
Argument (Pulse
number)
{
s+1
Argument (Frequency
value)
{
s+2
Argument (Number of
output pulses)
{
Function
Pulse output number:
H01 to H04
Change specification:
H00: Sets the frequency value and
number of pulse output,
H01: Sets the frequency value
only,
H02: Sets the number of pulse
output
Frequency: 10 to 5000 (Hz)
* The maximum frequency of 5000 Hz represents the total of
all pulse output frequencies.
* If the frequency value is set to less than 10 Hz, it is
internally changed to 10 Hz. The S parameter is also
rewritten.
Number of output pulses: H0000 – HFFFF (0 to 65535)
Auto correction is executed when the value corresponding to
the CPU model is specified in WRF06B.
Caution: There will be a slight error even if correction setting
is performed.
•
Pulse output is commenced at the specified frequency. Output is stopped once the number of pulses specified have been
output.
•
Sets the frequency value in Hz.
Example: To set a frequency of 3 kHz, set 3000 (HBB8) as internal output.
•
Sets the count for the number of output pulses.
Example: To set output of 10,000, set 10,000 (H2710) as internal output.
S
15
0
S + 1
Frequency value
S + 2
Number of pulse output
Pulse output number
Change specification
FUN 150 (s
)
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...