Parameter Description
Parameters
81
ACK
Inverter station
number
0
CR
H06
H30 H30
H0D
Step 3. The position machine requests the inverter for reading the value P.195 using Format
B:
ENQ
Inverter station
number
0
Reference code
H5F
Waiting
time
Check code
Sum check
CR
H05
H30 H30
H35 H46
H30
H30 H42
H0D
First 195 minus 100 equals to 95, then convert 95 to H5F hexadecimal digits. Next convert 5 and into H35
and H46, respectively, in ASCII code.
Step 4. Once the inverter receives and processes the data without error, the value of P.195
will be sent to the position machine in Format E:
STX
Inverter station
number
0
Read-out data
H1770(60Hz)
Unit
ETX
Check code
Sum check
CR
H02
H30 H30
H31 H37 H37 H30
H32
H03
H36 H31
H0D
Example 4.
Change the content of P.195 to 50 (the original factory setting is 60).
Step 1 to 2: Omitted (Same as Step 1 to 2 of Example 3);
Step 3: The position machine requests the inverter to write 50 in P.195 in Format A:
ENQ
Inverter station
number
0
Reference
code
HDF
Waiting
time
Data
H1388
Check code
Sum check
CR
H05
H30 H30
H44 H46
H30
H31 H33 H38 H38
H45 H45
H0D
First, 195 minus 100 equals to 95; because the smallest unit of P.195 is 0.01,
Concert 95 to H5F hexadecimal digits, 50 x 100 = 5000; then convert 5000 to hexadecimal
H5F+H80=HDF digits H13888; Then covert 1, 3, 8 and 8 to ASCII
codes for transmission.
Step 4. After receiving and processing the data without error, the inverter will send a reply to
the position machine in Format C:
ACK
Inverter station
number
0
CR
H06
H30 H30
H0D